Product Code |
K21001M2 |
Size |
385mm(W) x 310mm(H) x 110mm(D) |
Construction |
1.2mm mild sheet steel |
IP Rating |
IP30 |
Finish |
Epoxy powder coated |
Colour - lid & box |
BS 00 A 05 grey - fine texture |
Colour - controls plate & labels |
RAL 7047 light grey - satin |
Weight |
7kg |
Areas |
1 |
Mains supply |
230V AC, 50Hz +10% - 15% (100 Watts max.) |
Mains supply fuse |
1.6 Amp ( F1.6A L250V) |
Power supply rating |
5.25 Amps total including battery charge 28V +/- 2V |
Maximum ripple current |
200 millivolts |
Battery type |
12 Volt sealed lead acid |
(Yuasa NP) |
in series |
Maximum Battery Capacity within Enclosure |
Yuasa 7Ah |
Battery charge voltage |
27.6VDC nominal (temperature compensated) |
Battery charge current |
0.7A maximum |
Battery fuse |
20mm, 3.15A glass |
Current draw in mains fail condition |
54 milliamps |
Maximum current draw from batteries |
4 Amps |
Aux 24V output |
Fused at 500mA with electronic fuse |
1st and 2nd stage Sounder outputs |
21 to 28V DC Fused at 1A with electronic fuse |
Fault relay contact rating |
5 to 30VDC 1A Amp maximum for each |
Fire relay contact rating |
5 to 30VDC 1A Amp maximum for each |
Local fire relay contact rating |
5 to 30VDC 1A Amp maximum for each |
First stage contact rating |
5 to 30VDC 1A Amp maximum for each |
Second stage contact rating |
5 to 30VDC 1A Amp maximum for each |
Extract contact rating |
5 to 30VDC 1A Amp maximum for each |
Zone quiescent current |
0mA minimum, 2mA maximum |
Terminal capacity |
0.5mm2 to 2.5mm2 solid or stranded wire |
Number of sounders per circuit |
Dependent on type and current consumption |
Monitored input end of line |
6K8 +/- 5% ½ Watt resistor |
Sounder circuit end of line |
10K +/- 5% ¼ Watt resistor |
Extinguishant output end of line |
1N4004 Diode |
Extinguishant release output |
21 to 28V DC. Fused at 1 Amp |
Extinguishant release delay |
Adjustable 0 to 60 seconds (+/- 10%) |
Extinguishant release duration |
Adjustable 60 to 300 seconds |
Monitored inputs normal threshold |
(Allowable EOL) 10K ohm to 2K ohm |
Monitored inputs alarm threshold |
2K ohms to 150 ohms +/- 5% |
Monitored inputs Short circuit threshold |
140 ohms to 0 ohms +/- 5% |
Status unit/Ancillary board connection |
Two wire RS485 connection (EIA-485 specification) |
Status unit power output |
21 to 28V DC, Fused at 500mA with electronic fuse |
Extract contact rating |
5 to 30VDC 1A Amp maximum for each |
Zone quiescent current |
0mA minimum, 2mA maximum |
Terminal capacity |
0.5mm2 to 2.5mm2 solid or stranded wire |
Number of detectors per zone |
Dependent on type - typically 20 |
Number of sounders per circuit |
Dependent on type and current consumption - typically 20+ |
Detection circuit end of line |
6K8 +/- 5% ½ Watt resistor |
Monitored input end of line |
6K8 +/- 5% ½ Watt resistor |
Sounder circuit end of line |
10K +/- 5% ¼ Watt resistor |
Extinguishant output end of line |
1N4004 Diode |
No. of detection circuits |
Two to eight. 21 to 28V DC |
No. of sounder circuits |
Dependent on model 21 to 28V DC |
Extinguishant release output |
21 to 28V DC. Fused at 1 Amp |
Extinguishant release delay |
Adjustable 0 to 60 seconds (+/- 10%) |
Extinguishant release duration |
Adjustable 60 to 300 seconds |
SIL, AL, FLT, RST inputs |
Switched -ve, min resistance 0 ohms, max resistance 100 Ohms |
Zone normal threshold (Allowable EOL) |
10K ohm to 2K ohm |
Detector alarm threshold |
1K ohms to 390 ohms |
Call point alarm threshold |
370 ohms to 150 ohms |
Short circuit threshold |
130 ohms to 0 ohms |
Head removal condition |
15.5 to 17.5 volts |
Cabling |
FP200 or equivalent (max capacitance 1uF max inductance 1 mH |
Monitored inputs normal threshold (Allowable EOL) |
10K ohm to 2K ohm |
Monitored inputs alarm threshold |
2K ohms to 150 ohms +/- 5% |
Monitored inputs Short circuit threshold |
140 ohms to 0 ohms +/- 5% |
Status unit/Ancillary board connection |
Two wire RS485 connection (EIA-485 specification) |
Status unit power output |
21 to 28V DC. Fused at 500mA with electronic fuse |